久久无码人妻一区二区三区午夜_久久久久精品久久久久影院蜜桃_亚洲综合欧美色五月俺也去_交换娇妻呻吟声不停中文字幕

吉泰精密儀器(沈陽)有限公司
中級會員 | 第3年

17640053769

管道漏風量計算方法-SMACNA,美標US講解分析

時間:2024/2/22閱讀:242
分享:

一、法規(guī)概述

標準

國家

描述

SMACNA HVAC Air Duct Leakage Test manual, First edition, 2012

US

Duct construction leakage classification, expected leakage rates for sealed and unsealed ductwork, duct leakage test procedures, recommendations on use of leakage testing, types of test apparatus and test setup and sample leakage analysis.

 

二、法規(guī)詳情

法規(guī)內(nèi)要求的計算公式如下:

Duct Class

1/2-, 1-, 2-inwg

3-inwg

4-, 6-, 10-inwg

Seal Class

C

B

A

Sealing Applicable

Transverse Joints Only

Transverse Joints and Seams

Joints, Seams and All Wall Penetrations

Leakage Class

Rectangular Metal

16

8

4

Round Metal

8

4

2

Maximum air leakage is then defined as

F=CLP0.65 

F = Maximum air leakage (cfm/100 ft2)

CL = Leakage class

P = Pressure (inwg)

三、細則分析

1)法規(guī)要求下的最大限值Fmax

以美國標準為例,測試時由客戶提出密封等級(Seal Class)和測試壓力P,

根據(jù)SMACNA標準確定Leakage Class CL,根據(jù)公式 F=CLP0.65  計算出最大泄漏率Fmax

為方便計算,提供如下測算表:

Allowable Leakage Factor (CFM/100 sq ft)




Static pressure

0

1

2

3

4

6

7

8

9

10

CL

1

0.0000

1.0000

1.5692

2.0423

2.4623

3.2048

3.5425

3.8637

4.1712

4.4668

2

0.0000

2.0000

3.1383

4.0847

4.9246

6.4096

7.0851

7.7275

8.3423

8.9337

3

0.0000

3.0000

4.7075

6.1270

7.3869

9.6143

10.6276

11.5912

12.5135

13.4005

4

0.0000

4.0000

6.2767

8.1694

9.8492

12.8191

14.1701

15.4550

16.6847

17.8673

6

0.0000

6.0000

9.4150

12.2541

14.7737

19.2287

21.2552

23.1825

25.0270

26.8010

8

0.0000

8.0000

12.5533

16.3387

19.6983

25.6382

28.3403

30.9100

33.3693

35.7347

12

0.0000

12.0000

18.8300

24.5081

29.5475

38.4574

42.5104

46.3649

50.0540

53.6020

16

0.0000

16.0000

25.1067

32.6775

39.3966

51.2765

56.6805

61.8199

66.7387

71.4694

24

0.0000

24.0000

37.6600

49.0162

59.0949

76.9147

85.0208

92.7299

100.1080

107.2041

 

 

舉例如下:

Static pressure :  6

CL :6

則F = 19.2287  即最大限值Fmax

2)實測管道的測試值F

 測試值F.png

QL—泄漏風量值(cfm)

Area—被測管道的表面積(ft2)

3)判定

F<Fmax則被測管道合格

 

GTI 管道漏風量測試機型號DALT6900,DALT6910儀器內(nèi)置以上標準,無需計算,可以直接輸出判定結果,操作簡單方便!